5 Must-Have Features in a Hot Oil Boiler

10, Mar. 2025

 

Hot oil heaters and thermal fluids: the complete guide - Pirobloc

Thermal stability. Maximum operating temperature

The thermal stability of the fluid is the primary factor for determining its maximum operating temperature.

You will get efficient and thoughtful service from gtboiler.

Thermal stability is defined simply as the ability of a heat transfer fluid to withstand the molecular cracking of the thermal stress. The relative thermal stability test for heat transfer fluids measures the molecular bond strength of a fluid at a specific temperature compared to another fluid at the same temperature and under identical test conditions.

The tests are carried out under ideal laboratory conditions and do not take into account operational stresses such as mechanical failures, design defects, oxidation, etc. and, therefore, the data generated are only useful for comparative purposes. The exact predictions for the life of the fluid in actual processes should not be taken from the thermal stability data.

The maximum operating temperature is the maximum temperature recommended by the fluid manufacturer at which it can be used in continuous use while still maintaining an acceptable level of thermal stability. Because the degradation rates of the fluid are closely linked to the temperature, habitually working above the maximum operating temperature of the fluid will exponentially increase the degradation rate.

Potential problems caused by excessive degradation and the subsequent formation of degradation by-products include increased coking and dirt, mechanical difficulties and a decrease in heat transfer efficiency.

Therefore, as you could probably imagine, the first step in the process of selecting a particular type of thermal oil is to establish the maximum operating temperature. As mentioned above, most mineral oils have a maximum recommended temperature of between 270°C and 315°C, whereas the synthetic or aromatic thermal fluids are especially recommended for maximum fluid temperatures of between 315°C and 400°C.

Given that the molecular structures of aromatic compounds are significantly more thermally stable than mineral oils above 280°C, synthetic fluids are also recommended in applications above this temperature.

Process applications that require fluid temperatures of between 150°C and 280°C can specify either synthetic or petroleum based fluids, with other characteristics being used to determine the choice of thermal fluid.

Heat Transfer Efficiency

When assessing this property, it should be noted that greater efficiency in heat transfer does not, in most cases, represent an economic saving in fuel (which basically depends on the design of the boiler) as may initially appear, but this property will result in less time in obtaining the energy objectives of our process. Thus, with equal exchangeable surfaces in our consuming apparatus, we will reach the required operating temperature faster if the heat transfer fluid has a high heat transfer efficiency.

Comparisons of heat transfer efficiency between different heat transfer fluids are made using heat transfer coefficients. At a specific temperature, the overall heat transfer coefficient of a fluid can be calculated using its density, viscosity, thermal conductivity and specific heat (see spreadsheet on properties of thermal fluids) at a given flow rate and pipe diameter.

The resulting heat transfer coefficients can be evaluated and compared. At a given temperature, the heat transfer coefficients of the various types of heat transfer fluids may differ by 25%. Depending on the thermal resistance factors of the other components of the system, a fluid with a considerable heat transfer coefficient advantage may permit a reduction in the size of the system equipment.

Most synthetic thermal fluids have a significant advantage over mineral oils in heat transfer efficiency at temperatures between 150°C and 260°C. Above this temperature range (up to 300°C), some mineral heat transfer fluids narrow the gap with highly refined paraffinic / naphthenic white oils.

It must be remembered that the heat transfer coefficient is calculated using the factory supply properties of the heat transfer fluid. Fluid which has been in service for an extended period of time and which has undergone thermal degradation may have a lower coefficient due to changes in the viscosity of the fluid and the presence of less efficient fluid degradation by-products. Therefore, the thermal stability of a fluid plays an important role in maintaining its thermal efficiency over time.

Minimum pumping temperature

This temperature, and not the freezing point, is the temperature at which a heat transfer fluid can operate. It is defined as the temperature at which the viscosity of the fluid reaches a value, typically cps, at which centrifugal pumps cannot circulate the fluid.

Although most process applications are run at temperatures well above this point, system designs may encounter problems during emergency shutdowns or maintenance shutdowns if we have not taken this requirement into account in the acquisition of our system's heat transfer fluid.

Generally speaking, most mineral heat transfer oils and mid-range synthetic fluids have start-up values in the range of -20ºC to -5ºC. High-end synthetic fluids ' aromatic synthetic fluids with biphenyl / diphenyl oxide and with maximum operating temperatures of 370°C ' 400°C, have values of 5°C ' 15°C as their minimum pumping temperatures.

Processes that utilize a heat transfer fluid that may potentially have cold start-up problems will require a heat source in their pipework, using either steam or electrical resistance.

Environment

A comparison of the environmental and personal safety guidelines is important when selecting a specific chemical fluid. NONE of the heat transfer fluids present a significant health hazard when used in accordance with sound handling practices.

Most thermal fluids are non-toxic in terms of both contact with the skin and ingestion. Only a few aromatic synthetic fluids with biphenyl / diphenyl oxides have some different characteristics in these respects.

Investment, Economic cost

As a general rule, the higher the maximum temperature of use of the fluid, the greater the economic cost.

Medium-range synthetic heat transfer oils with operational temperatures of up to 340°C are between one and a half to two times more expensive than mineral oils, while high-end aromatic synthetic heat transfer oils for working temperatures of up to 400°C are up to five or six times more expensive.

Within this criterion of economic cost, it is important to include operating costs such as maintenance, replacements, etc. In order to minimize these, we recommend following the recommended heat transfer fluid sample analysis program, both in terms of frequency and in terms of the parameters evaluated (see analysis of heat transfer fluids).

This allows the user to be perfectly informed on the condition of the current heat transfer fluid charge and to minimize maintenance stoppages and excess costs due to energy inefficiency as a result of degradation.

Visual inspection

Many problems with the fluid can be detected by its appearance and smell.

For example, fine black sediments at the bottom of the sample container generally indicate the accumulation of solids. Liquid contaminants may appear as a separate layer at the bottom of the sample.

Water has a very low solubility in most thermal fluids and can be noticed in most cases with the naked eye. Water in the equipment causes circulation problems, cavitation of the pumps, excessive pressurization and premature oxidation of the thermal fluid.

Contaminants soluble in synthetic, aromatic based thermal fluids will affect the odor of the sample.

A quick, practical test to determine if there are carbon particles in the fluid is to turn the sample container upside down after 24 hours and look for soot at the bottom of the container.

Fine carbon particles, similar in appearance to dirt, form from oxidation decomposition. They are produced inside the boiler and under normal operating temperatures.

These particles remain suspended in the thermal fluid while it flows, but can coalesce in sufficient quantities to form blockages. These carbon particles settle when the liquid is not circulating.

Expansion tanks have a higher risk of this type of sediment formation, when it is usually known as sludge.

Chemical analysis

All the properties tested are intended to indicate the thermal fluid load status to determine if it needs substituting to ensure proper operation.

The parameters tested to establish the thermal fluid load status are different from those for checking lubricating oils or hydraulic fluids. In addition, thermal fluids operate in closed loop systems without any continuous exposure to air, unlike lubricating oils or hydraulic fluids which operate in open systems with continuous exposure to air.

Although there are many parameters providing indications of a thermal fluid load status, usually a visual inspection as indicated above and 3 more provide a fairly accurate view.

These 3 parameters are: the acid number, viscosity and flash point.

A more extensive analysis may be necessary only if contradictory or doubtful values are found for the indicated parameters.

Acid or neutralization number

This measures the amount of acid present in the liquid from the mass (in milligrams) of potassium hydroxide (KOH) required to neutralize one gram of the sample; this indicates the amount of oxidation that has occurred. The higher the acid number, the more oxidation will have occurred.

When the thermal fluid reacts with oxygen (oxidation), organic acids are produced. This occurs as a result of the equipment not being perfectly sealed, allowing the ingress of air (mainly) and water.

Sludge deposits and a high viscosity are symptoms of oxidation and are the most common reasons for fluid degradation. However, unless there is water present, these acids are not corrosive in the traditional sense.

Most oxidation products are soluble in the thermal fluid and reactions take place between them, forming sludge, especially at points where sedimentation is favorable; for example, in the expansion tank, as previously indicated. However, other oxidation products are insoluble and can lead to deposits, partial clogging of pipes and accelerated mechanical deterioration of seals, valves and pumps, for example.

Viscosity

This measures the fluidity of the fluid. The value obtained is usually compared with that of new fluid, with the results sometimes being shown as a percentage in relation to the change. The comparison with new fluid values is necessary, since viscosity is proportional to the average molecular weight, and can therefore have very different values according to the composition of the fluid. This test alone, however, is not sufficient to establish the fluid status with certainty.

The property of it being proportional to molecular weight is what makes any change in viscosity suggest changes in fluid composition. However, it must be remembered that only extreme changes are significant. These extreme changes can be caused either by oxidation (confirmed by acid number values) or chemical cracking, overheating or contamination.

Flash point

This gives an indication of the presence of volatile compounds in the fluid. As with the viscosity determination, its value should be compared with that of the new fluid, as there are significant differences in the flash point, depending on the type of thermal oil.

It is one of the characteristic temperatures of thermal fluids (see 'Characteristic temperatures of thermal fluids').

There is no standard or regulation covering the allowed change of flash point in a thermal fluid. However, this parameter is indicative of the amount of more volatile fractions (low boilers) found.

A fluid whose flash point is significantly less than its original value will have a higher concentration of lower boiling point molecules.

Significant decreases in test results may indicate that degradation has occurred.

Other usual parameters

Although it is difficult to determine them in routine analyses, the boiling range and carbon residue are also parameters that are often evaluated.

Boiling range

Because thermal fluids are made up of different components and additives, each with its own boiling point, the liquid will evaporate over a range of temperatures called the boiling range.

The higher that range is, the greater the degradation.

Carbon residue

This indicates the tendency of the fluid to form carbon deposits when subjected to high temperatures.

The analysis values found are from residues of the product under standardized test conditions, which evaluates their quantity and appearance to judge the degree of refining and nature of the oil.

Obviously, the higher the value, the greater the degradation.

Results

Laboratory data provide only a snapshot of the fluid status. This is why trends that become apparent after several routine samples have been taken are important.

The data must be placed in a time perspective together with the equipment operational history and knowledge about it to correctly interpret the results, obtain a complete analysis of the system and determine if the analyzed load can continue in service or has degraded to a point that a change is necessary.

Under normal working conditions, with the appropriate maintenance operations and moving within the operation parameters of the chosen heat transfer fluid, it is considered that the useful life of a charge should be in the order of - effective hours.

This useful life may be higher if the characteristics of the heat transfer fluid are much greater than those required by the system.

If a load change is not due to the fluid reaching the end of its useful life but to so-called 'external conditions' resulting in accelerated degradation, changing the fluid could become routine unless these conditions or problems are corrected.

Obviously, if it has reached this point, it is due to a lack of routine control. As, if it were not the case, analytical results would have provided the necessary information to identify problems and their origin. Thus, the necessary corrective actions would have been implemented before the continued use of the fluid would have compromised the equipment efficiency or service.

Along with the analytical results, it is customary to refer to the standard under which the different tests have been carried out; as the values obtained may differ according to the standard and lead to misunderstandings in their interpretation.

For example, the flash point determined by the so-called closed cup or Pensky-Martens method gives values approximately 20°C lower than that determined with the so-called open cup or Cleveland method.

Also, specifying the standard under which the analyses have been carried out implies a rigor in their implementation and therefore a reliability in the results obtained.

DIN (Germany) ASTM (USA) IP (GB) NF (France) Flash point 'open cup' (Cleveland) D 92 36 T Flash point 'closed cup' (Pensky-Martens) D 93 34 M Kinematic viscosity D 445 71 T Acid or neutralization number D 974 139 T Boiling range D 480 M Conradson carbon residue D 189 12 T Table of the most general analytical standards for the values tested

Thermal fluids degrade over time due to thermal cracking and oxidation. As already mentioned, the degradation speed can be influenced by inadequate operating procedures, bad design or contamination.

Therefore, the first suggestion is obviously to have proper equipment design, adapted to the needs of the process with the thermal fluid that best meets the technical requirements being selected.

The second step is to operate under the design conditions, without extreme temperatures or design power, and with efficient preventive and corrective maintenance procedures.

Below is a list of good practices to ensure the useful life of the thermal fluid load is as expected.

Oxidation

As already indicated, thermal fluids react with air to form organic acids. The oxidation rate is low at ambient conditions but increases rapidly with temperature.

These acids can be subjected to the polymerization of free radicals that increase the viscosity of the fluid and, ultimately, give rise to sludge deposits.

Minimizing oxidation and lengthening the load deterioration process due to this reason is relatively simple:

  1. The equipment must be designed to be properly sealed, either by the so-called 'hydraulic cushion' method or by other systems, including the use of inert gases. Check that whatever system used in the equipment design works correctly, with enough hydraulic cushion and the proper nitrogen pressure.
  2. The design should also ensure that the temperature in the expansion tank is kept below 70°C.  ' Do not insulate the expansion tank or the pipes connected to it.
  3. Perform maintenance operations with the fluid at temperatures below 60°C.
  4. Replace mechanical pump seals and gaskets only if leaks are detected. Whenever the equipment stops, the entry of air may be facilitated by a vacuum occurring at those points.
  5. Before any modification or expansion of the equipment, it must be re-commissioned by repeating the initial dehydration process.

Pollution

Contaminants can lead to the degradation of the fluid, as well as cause operational problems.

Contaminants can enter the system in several ways:

In new equipment

New equipment requires parts to be manufactured and assembled in the field, usually tubing, with a degree of cleanliness at least equivalent to the components to be joined and which have been supplied clean and protected from the factory.

A frequent problem in thermal fluid equipment is contamination of the fluid during assembly, due to cutting and welding operations, dust and dirt, the use of protective lacquers, poor component storage or improper handling during the load filling process.

The method of cleaning and purifying a thermal fluid in new equipment is called 'Flushing'

Once the equipment is completed, it can undergo similar contamination during the fluid operational phase, with solid particles or water.

This contamination affects both the system pipes and components, so the initial cleaning level must be recovered.

Solid particles can be removed by using filters that have to be cleaned regularly, while verifying the pump suction pressure does not fall below normal service levels. If so, it is indicative of dirt in the filter.

The presence of water almost certainly means there are leaks in the heat exchangers, which must obviously be repaired.

Pressure testing

Another reason for water in the equipment may be due to pressure testing of any part of the equipment with water. This would be detected immediately after re-connecting the equipment involved, and can be removed by purging the system.

These cases should be avoided by requiring the equipment suppliers to carry out pressure testing with the thermal fluid at installation, as it is extremely difficult to dry properly.

Water may also be present from condensation in the expansion tank, which would be due to inadequate design of the sealing system and the presence of air might also be quite feasible.

Thermal cracking or overheating

Chemical cracking is decomposition of a product, in this case thermal fluid, into high and low boiling point components, due to exceeding the maximum recommended thermal fluid film temperature (see Characteristic temperatures of thermal fluids).

Another, 'more graphic' description, is to say the different product component bonds break and it no longer behaves uniformly. The decomposition is divided into 'low' and 'high' boilers.

The first group consists of the most volatile fractions in the fluid, which evaporate and are eliminated to the outside by the expansion tanks.

This causes non-uniform warming and pump cavitation.

The second group is composed of thermal fluid substances which are carbonized and adhere to the walls of the coils.

Initially, this incipient cracking decreases the boiler performance as these products become pseudo-insulators with the increase in fuel that this represents with the obvious production difficulties.

However, the next step is even worse. As the fluid degrades, a smaller amount of heat passes through the coil pipes and the temperature of the wall increases.

This burns out and destroys the coils and the boiler has to be replaced.

Cracking can be minimized or prevented:

  1. Attention must be paid to the safety devices installed and maintenance of this instrumentation performed. Cracking is not possible using regulatory safety devices which function properly. Using high temperature and/or low flow alarms which indicate overheating can avoid cracking if they are considered and evaluated
  2. Consider a properly designed installation from the start, with thermal fluid according to your needs, but be very careful in the selection of a pump change for any circumstance, as cracking can be caused by a lack of thermal fluid flow in the boiler.For any modification or extension of the initial circuit, resort to a professional hydraulic redesign of the equipment, as this may require replacing the initial pumps. The equipment must be re-commissioned.
  3. Do not start the system at full power. Heating progressively until reaching the temperature of 100°C minimizes the thermal stress of the fluid.
  4. Also, avoid sudden stops, and let the fluid circulate until the outlet boiler temperature is around 100°C.
  5. The burner must provide the design power of the existing boiler and be properly adjusted.
  6. Power failures are common, so you should consider connecting the pump to an auxiliary power supply.
  7. Perform routine analysis of thermal fluid samples taken from your equipment and follow the recommendations of the results. Cracking can occur because you want to extend the useful life of a load that should have been replaced earlier due to another cause, e.g. oxidation.

The values of the characteristic temperatures are the result of laboratory tests, under specific standards that establish the parameters of the test ' tangential incidence of spark, strict environmental control, specific temperature ramp up, etc., which are not present in normal circumstances but which allow baseline values to be established.

According to the specifications and, therefore, the standards used, there may be variations in the values obtained, although all of them will be very similar.

For this reason, the results obtained must include the standards under which the test was performed.

Maximum operating temperature

This is the maximum temperature recommended by the fluid manufacturer at which it can be used in continuous use while still maintaining an acceptable level of thermal stability.

Because the degradation rates of the fluid are closely linked to the temperature, habitually working above the maximum operating temperature of the fluid will exponentially increase the degradation rate.

Potential problems caused by excessive degradation and the subsequent formation of degradation by-products include increased coking and dirt, mechanical difficulties and a decrease in heat transfer efficiency.

Obviously, it is of extreme importance when selecting the most suitable heat transfer fluid for each of the production processes.

Maximum film temperature

In a boiler, the coil walls reach temperatures that are higher than the operating temperature of the heat transfer fluid.

The operating temperature of the heat transfer fluid is considered to be the one given at the section centre of the coils and is also often referred to as the mass temperature, while the film temperature is the temperature reached by the heat transfer fluid which is in contact with the wall of the coils.

This temperature always has a higher value than the mass temperature and if, under operating conditions, it exceeds the temperature defined by the manufacturer of the heat transfer fluid, the fluid will become thermally degraded. ' see figure 1 -.

This temperature is of vital importance in the design of the boilers.

Under operating conditions, with a correctly designed boiler and with the appropriate flow of heat transfer fluid, the film temperature is usually between 5 and 10°C higher than the mass temperature.

Freezing Point ' Pour Point

It is the temperature at which the heat transfer fluid is not able to flow by simple gravity because the viscosity has become infinite.

To reduce this point, heat transfer fluids are added, with most of the heat transfer fluids on the market having values around -30ºC.

Minimum pumping temperature

This temperature, and not the freezing point, is the temperature at which a heat transfer fluid can operate and must, therefore, be taken into consideration when selecting the heat transfer fluid.

It is defined as the temperature at which the viscosity of the fluid reaches a value, typically cps, at which centrifugal pumps cannot circulate the fluid.

Although most process applications are run at temperatures well above this point, system designs may encounter problems during emergency shutdowns or maintenance shutdowns if we have not taken this requirement into account in the acquisition of our system's heat transfer fluid.

Generally speaking, most mineral heat transfer oils and mid-range synthetic fluids have start-up values in the range of -20ºC to -5ºC.

High-end synthetic fluids ' aromatic synthetic fluids with biphenyl / diphenyl oxide and with maximum operating temperatures of 370°C ' 400°C, have values of 5°C ' 15°C as their minimum pumping temperatures.

Processes that utilize a heat transfer fluid that may potentially have cold start-up problems will require a heat source in their pipework, using either steam or electrical resistance.

Flash Point

This is the lowest temperature at which the vapours produced by the heat transfer fluid will ignite, resulting in a sudden flash on the surface of the heat transfer fluid when there is a flame nearby or a spark occurs in the presence of oxygen. It does not matter if the resulting flash is distinguished immediately afterwards ' see figure 2.

It is a very important indication of the condition of the heat transfer fluid. Normal values are around 190ºC.

It must be remembered that a heat transfer fluid circuit is closed and there is, therefore, no presence of oxygen and combustion cannot occur without a leak.

It is very important not to confuse this temperature with the autoignition temperature or with the combustion temperature.

Fire Point

This is the temperature at which, when a flame or spark is nearby and in the presence of combustion air (oxygen), the flame that forms remains alight for at least 5 seconds. Normal values are around 210ºC.

Autoignition Point

This is the lowest temperature at which the heat transfer fluid ignites itself, without the presence of a flame or spark to initiate the combustion. Obviously, the presence of combustion air is required.

Thus, the temperature to be examined in the face of a possible leakage of heat transfer fluid is the autoignition temperature.

A leak would be necessary, since without it there would not be any oxygen in the circuit and, therefore, even if autoignition point temperatures were reached in a closed circuit, combustion would not be possible.

This is undoubtedly the type of boiler that you will most frequently come across and its design, with some variations and details, is very similar among many of the manufacturers in the industry.

Its assembly can be vertical or horizontal, depending on the needs of the user, but, in both cases, the concept and, therefore, the design are the same.

A boiler with a horizontal assembly allows it to be located in rooms that are relatively low in height and permits convenient and easy access to the burner and to the various parts of the equipment. By contrast, the greater needs for floor space with respect to a vertical boiler, can sometimes be a decisive element in the final decision.

As can be deduced from the previous paragraph, the location of the heat transfer fluid boiler is key in the selection of its orientation. The reason for this is that heat transfer fluid boilers, in almost all circumstances (only boilers with aromatic synthetic heat transfer fluids are excluded from this premise ' see heat transfer fluids), can be installed, in accordance with the regulations, as close as the user wants to the consumer appliances, offering the possibility to avoid long and expensive installations.

Description

The basic diagram for a heat transfer fluid boiler using liquid and gaseous fuels is shown in Figure 2.

The most common design is that of two concentric coils (8) and (9), within which the temperature of the heat transfer fluid increases by absorbing the energy  supplied by the burner (1), attached to the lid of the boiler (17). With just a single coil (and, therefore, two smoke passes) it is difficult to obtain good performance due to insufficient heat exchange surface, whereas using three or more coils, while guaranteeing high energy efficiency, also implies a high economic cost. Thus, the equipment with two coils and three smoke passes can be considered as the 'optimum design' that combines satisfactory yields with a moderate cost.

The inner coil performs the contour functions of the combustion chamber (5), establishing its diameter. The burner flame is projected from the burner to the combustion chamber, reaching, depending on the combustion adjustment, to just make contact with the ceramic tile (rear closure of the combustion chamber (13)) which delimits the length of the hearth. This is what is colloquially known as the first smoke pass.

Upon reaching the rear closure of the combustion chamber, the gases change direction and circulate at high speed and turbulence between the two concentric coils (second smoke pass (6)) to the front cover, where they change direction again until evacuated by the flue (14), through the passage between the outer coil and the inner casing (11) (third smoke pass).

In the vast majority of cases, the two coils are connected in series. Only specific designs for large flows and low heat differentials, require the coils to be connected in parallel (see technical concepts).

In order to achieve the airtightness of this smoke circuit, which is necessary to ensure the anticipated energy yields of the boiler, there are closures (13) and (18) which force the combustion gases to travel the path planned initially during the design of the equipment.

To promote heat exchange, the circulation of the heat transfer fluid is initially through the outer coil to then pass to the inner coil, thus being a counter-current exchange of temperatures with respect to the flue gases and achieving excellent energy yields.

The entire assembly is thermally insulated (10), (12) and (16), in order to minimize structural energy losses into the atmosphere, while avoiding possible burns by inadvertent contact with the surface of the boiler.

Key

1.- Burner
2.- Fuel supply
3.- Heat transfer fluid Output to consumer/system points
4.- Heat transfer fluid Return from consumer/system points
5.- Combustion chamber. Combustion gases, first pass
6.- Combustion gases, second pass
7.- Combustion gases, third pass
8.- Heat transfer fluid Interior coil
9.- Heat transfer fluid Exterior coil
10.- Thermal insulation of the boiler body
11.- Inner casing
12.- Base of the boiler
13.- Combustion chamber bottom closure. Ceramic tile/refractory concrete
14.- Chimney/flue
15.- Output of combustion gases
16.- Thermal insulation of boiler and combustion chamber
17.- Boiler cover
18.- Combustion chamber top closure

Heat exchange

For the purposes of heat exchange, the configuration described can be divided into three parts in accordance with the heat transfer method and in relation to the technical constraints that are required at each point, in order to achieve the energy efficiency and durability results from the heat transfer fluid charge and from the equipment materials. (see Heat transfer).

In Figure 3, the three zones are clearly distinguished:

1. Radiation

It encompasses practically the entire combustion chamber, more specifically, the inner face of the interior coil, with it being decisive in this area, from a technical point of view, to know the exact values of the maximum temperature reached by both the heat transfer fluid and the material of the coil because, although it is the area with the greatest exchange capacity, it is also at risk of exceeding the maximum permitted values. ' Figure 4 -.

The characteristics of the thermal fluid used, the fuel, the combustion regulation, the flame diameter, the exchange requirements, the minimum circulating flow of heat transfer fluid required and, therefore, its velocity and the diameter of the coil tube are all parameters that determine what must be considered as critical in the design ' the dimensioning of the diameter and the length of the chamber.

A too small diameter for the combustion chamber would allow an optimum transfer of heat but would jeopardize the useful life of the charge of heat transfer fluid as well as of the boiler itself and would also cause a loss in the smoke circuit charge which may be an excessive burden for a standard burner.

On the other hand, a combustion chamber with an over-sized diameter, will decrease the energy efficiency of the equipment.

The length of the combustion chamber is also of great importance with respect to the reliability of the equipment. A combustion chamber that is too short for the power required would involve unusually high temperatures in the bottom closure and in the upper closure of the chamber, which could lead to the partial destruction of these elements.

2. Transition zone

This comprises the inner faces of the ends of the inner and outer coils. Depending on the adjustment of the burner, it may partially include the outer face of the inner coil. In this area, radiation and convection coexist as heat transfer processes and, therefore, with regard to the heat, both the precautions for exchange by radiation and the constraints due to exchange by convection must be taken into account.

Particular attention should be paid to the design for the change in direction of the combustion gas circuit in the bottom closing of the combustion chamber, since complete airtightness must be achieved (otherwise the combustion gases would pass directly from the 1st pass to the flue outlet, giving very poor performance and worse, with extremely high temperatures in the flue that could cause its destruction) together with a low loss of charge in the change of direction of the flue gases.

3. Convection zone

This corresponds to both faces of the outer coil and the inner face of the interior coil.

Although there may a slight risk of exceeding the maximum temperatures of use of heat transfer fluid and materials (see Figure 4), the main concern when designing this area is that of achieving a high level of heat transfer by means of a considerable velocity of combustion gases but without producing significant contamination risks in smoke passes 2 and 3 owing to under sizing in these passages or a high loss of charge in the smoke circuit (known as boiler overpressure) making it difficult to use standard market burners.

In addition to all of the parameters discussed above, the coils should also be carefully designed so that, from the hydraulics point of view, the heat transfer fluid circuit charge losses are not high, which would result in non-standard pumps and high electricity consumption and which, at the same time, guarantees sufficient heat transfer fluid velocity in order to provide satisfactory heat transfer coefficients ' see Figure 5.

Heat differential. Passes in the coils

Heat differential also known as heat jump, is the maximum increase in temperature of the heat transfer fluid that a boiler is able to obtain in its nominal heat power, at the design flow rate of heat transfer fluid.

The most common thermal jumps are 20°C and 40°C, although these values have some margins depending on the heat transfer fluid used and the operating temperature, thus, we should actually talk about intervals of between 18-22°C in the first case and 36-42°C in the second case.

It is important to keep in mind that one boiler is not better or worse than another boiler with the same heat power but a different jump. With the correct design, both types of boiler will have similar energy performances and similar operating functions.

The reason for having boilers with different heat differentials is to obtain the best adaptation of the boiler to the characteristics of the production process and, more specifically, to the system's consumer appliances.

Initially, a boiler with a 20ºC heat jump can give a greater uniformity of temperature in the consuming appliances due to having a greater circulating flow, although with an initially more expensive installation due to a larger pipe diameter, more heat transfer fluid capacity in the system and a higher electrical consumption in the main pump. However, a boiler with a 40°C heat differential can also achieve the same results by means of recirculation circuits with secondary pumps which provide a greater flow rate in consumer appliances and, thus, greater uniformity. In the latter case, however, the installation cost of the heat differential boiler is considerably higher which is not a positive factor.

Heat differentials higher than 40 or 50ºC are not common given that the useful life of the heat transfer fluid is affected by such high and abrupt changes of temperature and the design of the boiler must anticipate measures for absorbing additional expansions, which makes the design more specialized and more expensive. However, in applications for solar thermal power plants, heat transfer fluid boilers with heat differentials of 100°C can be found.

Our recommendation is that the user contact the boiler manufacturer, authorized installer or in-house or external engineer to discuss what heat differential would be the most suitable for their process.

We have already seen that determining the heat differential, basically by the characteristics of the consuming devices, determines the circulating flow rate of heat transfer fluid required in the system. But this flow must also meet certain requirements marked on the boiler.

The velocity of the heat transfer fluid in the coils must be high enough to ensure a good heat exchange while not exceeding the film temperature of the heat transfer fluid used in order to avoid its rapid degradation. But these high circulation speeds that are required also imply significant charge losses (pressure losses) since the charge loss is proportional to the high velocity squared, with the possibility of having to resort to very large pumps with inordinately high electricity consumption in order to achieve hydraulic stability in the circuit.

Reconciling the factors of high velocity and acceptable charge losses is only possible with a precise heat and hydraulic study of the coils, the diameter of their tubes, the length of these and their connection.

With the help of the diagrams in Figure 6 and a short example, we will try to clarify a little all these issues. We have simplified the possible hydraulic options exclusively in these three cases. In reality, the parallel passes of the coils can be from only 1 pass or up to 6, 7 or 8.

The operating temperature T1 and its kW heat output are the same in all three diagrams in Figure 6. Also, the total length of the component pipe of the coils is the same ' 4L.

The differences relate to the boiler inlet temperatures (return temperature from the consuming appliances after supplying the required energy), T2, T3 and T4. The circulating flow rates Q, Q1 y Q2 and the charge losses ΔP1, ΔP2 and ΔP3 are also different.

Real numeric example

We have a heat transfer fluid boiler with 40ºC heat differential and with kW of heating power. Its exchange surface is 54 m2 with yields in the order of 86-89%, depending on operating temperature.

Its design outline is A) in Figure 6, with two coils in series and two parallel passes per coil. The design flow rate for these conditions is 52 m3/h, with a charge loss of 2.37 bar at 260ºC operating temperature.

If we try to operate this boiler with a heat jump of 20°C, the flow rate would have to be 104 m3/h and the expected charge loss at the same temperature as before, 260°C, would be 8.17 bar. We would have to resort to very sophisticated and expensive pumps, with very high electricity consumption.

On the other hand, if we use design outline B) in Figure 6 (two coils in series with three parallel passes per coil) with the same flow rate, 104 m3/h, and exchange surface, 54 m2, the charge loss would be 2.62 bar, which is acceptable for conventional pumps.

This type B) design outline would not be feasible for a boiler with a 40ºC heat differential since, with the low flow rate required, 52 m3/h, there would be no problems of pressure drop (only 0.71 bar) but, instead, the problem would be overcoming the fluid film temperature, since this would be approximately 44°C higher than the operating temperature.

If you want to learn more, please visit our website Hot Oil Boiler.

As can be seen in Temperatures, the maximum film temperature is usually in the order of 10-20°C above the maximum operating temperature so, in this hypothetical case, we would either suffer a rapid degradation of the heat transfer fluid charge or we would be forced to work at low temperatures, which may not be acceptable for our production system.

Design C), with two coils connected in parallel, each one with three passes of heat transfer fluid, corresponds to a fairly unusual assembly and one typical of boilers requiring very small heat differentials, in the order of 10 or 15ºC. Under these conditions, the flow rate, 205 m3/h, is very high and if this configuration were not chosen, the heat transfer fluid charge loss would be excessively high, even with the three-pass configuration in design outline B), given that it would be around 8.45 bar.

We can see, therefore, that the heat jump required greatly influences the design of the boiler and it must, therefore, be considered as a key factor in the installation project of a heat transfer fluid system.

Even though in many countries the cost of electricity is much higher than that of liquid or gaseous fuels, the absence of air pollution together with the absence of a need for a combustion gas flue means that heat transfer fluid electric boilers are often used in laboratories or in companies located in urban environments, as well as in companies in which strict respect for the environment is part of their business philosophy.

Other important advantages are the absence of fuel installations, which can sometimes require a significant amount of space, as well as the fact that they do not require a burner and therefore avoid the maintenance related to these, a particularly important point in companies with limited maintenance services.

Even with these advantages, the use of these types of heat transfer fluid boilers is limited to relatively small heat outputs since, due to the high economic cost of electric energy, they also require the availability of contracting the necessary power.

Its configuration is simple (see Figure 7), consisting of heating elements (5) welded to a flange (3) which serves to connect to another flange (4) of the cylindrical housing (2).

The heat transfer fluid (which is heated when it passes between the heating elements) flows within this housing and through inlet and outlet pipes (7) and (8). The junction or terminal box (1) is placed remotely in order to avoid the high temperatures. The housing is thermally insulated to avoid losses into the atmosphere and the risk of burns by inadvertent contact.

It is usually assembled horizontally to enable lower temperatures in the terminal box and to allow easy access to the same and to the elements for maintenance operations. However, occasionally, due to space requirements in the plant, they may also be assembled vertically (Figure 8); in these cases, the remote distance of the terminal box is greater.

If the power required is high, several groups of resistive elements, connected in series or parallel, can be assembled ' see Figure 2.

The electrical resistive elements that provide the energy to the heat transfer fluid must be those specified for this type of operation. A correct determination of the specific surface charge (W/cm2) of the heating elements is essential.

Factors such as heat transfer fluid characteristics and process parameters including minimum flow, inlet and outlet temperatures, maximum temperature regarding heating elements and the type and number of fastening rings (heat deflector plates) mounted on the element's surface.

All of this is intended to avoid deterioration of the heat transfer fluid charge due to exceeding the film temperature (see Temperatures), as well as overheating of the resistive elements. The deflector plates ensure a good circulation and hence a more uniform dissipation of the transferred energy.

The usual specific charges of heat transfer fluid in electric boilers are around 1.5 ' 3 W/cm2 in the design known as the 'container design', which is the most common and the configuration of which we have described.

In another type of design, known as the 'tubular design', used for very specific processes, where the heating element is inserted in a tube and, therefore, the heat transfer fluid can acquire high speeds, specific charges of up to 6 W/cm2 are used.

This requires special care at the beginning of the process, as the heat transfer fluid is more viscous at low temperatures and a high specific charge can cause overheating.

As a comparison, for other types of fluids such as water, it is usual to work with charges of up to 12 W/cm2.

Now speaking strictly about heat recovery boilers, their basic principle is the same, regardless of the origin of the gases, and is that shown in Figure 10.

Key

1.- Heat recovery boiler
2.- Gases produced by furnace, process or boiler
3.- Intake of heat transfer fluid to the heat recovery boiler
4.- Output of heat transfer fluid
5.- Chimney/flue
6.- Safety Flue
7.- Bypass

Heat is recovered from the gases produced by a furnace, a boiler or from a production process, by means of a heat recovery boiler (1) installed in the flue (2). The heat transfer fluid (3) and (4) is heated therein and the gases, once the heat has been transferred, are released into the atmosphere through a chimney/flue (5).

In this diagram the installation of a bypass (7) is essential, to allow adjustment of the heat supply to the heat recovery boiler, thus allowing the heat transfer fluid to reach the desired temperature.

If this temperature is reached, assuming that the activity that provides the energy via the gases cannot be stopped (because in most cases it would cause a serious loss of production), these gases are then diverted through the bypass to the safety flue.

Depending on the accuracy of the operating temperature that is required, the bypass can be either an all or nothing action or a modulated control.

Other auxiliary components of this configuration not indicated in the basic diagram are the silencers and expansion joints. It is important to remember that in some processes the temperature of the gases can be in the order of °C, therefore, considerable expansions are expected to be absorbed.

The great diversity in the characteristics of the heat recovery system, such as gas composition, aggressiveness of these gases, amount and type of ash, the required temperatures of the gas and of the heat transfer fluid, gas flow, heat differential of the heat transfer fluid, gas pressure at the intake of the heat recovery boiler and, therefore, the pressure that it can control, etc., etc., means that the design of heat recovery boilers is extremely varied and practically unique in each situation.

In images 3, 4 and 5, we can see various designs of heat recovery boilers: Double surround (suitable for high gas temperatures), battery-type with integrated bypass (medium power and temperature, but with significant amounts of ash), and inline chimney fan (specifically for using the flue gases of conventional boilers).

Figure 13 shows the two possible configurations of a combustion gas, heat recovery boiler taken from a conventional heat transfer fluid boiler.

In diagram A), the heat transfer fluid that flows through the heat recovery boiler belongs to the main system, by means of which the heat recovery boiler becomes an 'attached coil' or a 'third coil' of the conventional heat transfer fluid boiler.

Under these conditions a bypass regulator is redundant because the temperature control is performed via the usual safety features of the boiler, with there being no flue gases to be recovered if the burner is in the rest position after having reached the operating temperature and with there being no possibility of overheating.

Key

1.- Heat transfer fluid conventional boiler
2.- Burner
3.- Heat recovery boiler
4.- Heat transfer fluid return from consumer appliances
5.- Output of heat transfer fluid from the conventional boiler to consumer appliances
6.- Output of combustion gases from boiler
7.- Chimney. Gases into the atmosphere
8.- Heat transfer fluid inlet to conventional boiler
9.- Secondary line heat transfer fluid return
10.- Heat transfer fluid output to secondary line
11.- Bypass
12.- Safety flue

In diagram B), the recovery of heat makes it possible to make use of a network of heat transfer fluid independent from the main one, obviously, at an operating temperature lower than that one. In this scenario, the bypass regulator and a second flue are necessary.

The bypass can act exclusively as a safety device, performing temperature regulation and automatic valve functions for this secondary circuit.

Valves can be classified according to their function as follows:

Butterfly valves

Their function is to separate secondary branches, consumption devices, boilers or pumps from the general equipment, either for safety reasons or to carry out maintenance operations. They tend to be manually operated and are considered regulatory safety components. Points 1, 2, 3 and 5 of Fig.1

Control valves

They establish the required flow in consumption device branches to achieve the desired temperature in each of them; thus, the controllable quantity is the service temperature required in the apparatus. Point 12 of Fig.1, with a temperature indicator controller (TIC).

They are also used to determine the appropriate operating point in the facility pumps, to ensure the circulating safety flow by boiler, as necessary in the facility or branches. In the latter case, the amount to be controlled is usually a pressure or pressure difference. Points 4, 13 and 14 of Fig.1, with pressure differential (PD) control. As can be seen in this figure, the control valves can be manually operated (4) (14), usually for controlling the pump and are fixed in position, or electrically (12) or pneumatically (13) driven, to control the temperature in consumer appliances, with modulated regulation.

Depending on the hydraulic design of the facility, they can be either two- or three-way.

Safety Valves

Their function is to open if there is a pressure increase higher than the facility design values. They must be discharged to a safe location, usually a collection tank in the facilities. As there is no pressure/temperature relationship in the thermal fluid installations as marked in steam facilities, their presence is practically superfluous, although mandatory by regulation.

Check valves

An auxiliary component whose function is to prevent the circulation of fluid in directions not provided for in the design of the facilities.

They are useful to prevent anomalous situations, as the logical direction of the fluid is properly specified in the hydraulic study before implementation. Point 10 of Fig. 1. 1. They are also used to prevent pressures, but not circulation, at unwanted points in especially sensitive equipment; e.g. in a pump drive which is not in service. See Fig. 1a.

Filters

These must be able to retain impurities circulating through the facilities to prevent them reaching sensitive components, such as pumps or control valves. They are especially important in the start-up of the facilities, as there may be slag from welds made. After start-up, they are less important, as it is a closed circuit filtered beforehand.

However, if the thermal fluid begins to break down with the appearance of semi-solid waste, they have an important role again; as these residues accumulate in the filter and can be detected by a pressure loss control in it. Point 6 in Fig.1.

Auxiliary valves

These facilitate secondary operations to those of the process, whether for maintenance or putting into service conditions. Thus, there are valves in auxiliary circuits, such as filling/emptying (points 8 and 9 of Fig. 1) for making control components independent, such as pressure gages (point 7 of Fig. 1) and the visual level in the expansion tank (point 14 of Fig.1).

The following types are used:

Globe or seat

So called because of the spherical shape their body had originally, and although some designs are not as spherical at the moment, they retain the name because of the type of closing mechanism. The closure or shutter sits ' hence the name ' on a circular section. When actuating via the shaft or stem, the disc approaches the seat, the open section is reduced and the flow rate decreases. ' see Fig. 2 -.

The drive can be manual with a handwheel, which is usual when the valve is exclusively for interrupting functions; or electric or pneumatic, which is more suitable when the valve performs control or flow regulation functions.

Also the configuration and form of the disk may be different, especially in the degree it is cone-shaped, depending on the functions of the valve.

As thermal fluids tend to work at high operating temperatures, the seal tightness of all equipment components must be ensured, especially the valves. For this reason, it is customary or mandatory in some countries (e.g. in Spain, standard UNE 9-310) to use globe valves with extra packing as an addition to the standard packing ' see Fig. 3. 3 -.

Although globe valves can fulfil all the functions to be performed in thermal fluid equipment, in some of the additional or auxiliary operations, they are accustomed to using other types of valves that properly and safely comply with all the needs, but which are cheaper. If it is mandatory by statute, the use of globe valves with additional packing in butterfly valves ' points 1,2,3,4 and 5 of Fig. 1 and control valves ' points 12 and 13 of Fig. 1 1 -.

Ball valve

In a ball valve, a hollow sphere sits firmly completely blocking the flow of fluid. When acting on the handle, the ball rotates ninety degrees, which lets the fluid flow through the valve as it is hollow ' see Fig. 4. 4.

This type of valve allows practically no type of regulation on the circulating flow, as its action is basically of interruption: fluid passes or does not pass.

In thermal fluid equipment, these valves are used exclusively for auxiliary networks, such as those corresponding to system filling and emptying operations, which must be carried out at temperatures below 80°C, under which ball valves work with total reliability ' point 9 of Fig. 3. 3 -.

Fig 4. Ball valve

1. Handle ' 2. Body ' 3. Ball ' 4. Stem ' 5. Seat ' 6. Retainer/packing ' 7. Gland nut

Gate Valve

Gate valves open and close by lowering a gate structure, hence the name, inside them ' see Fig. 5. 5 -.

Most valves of this type are designed to be completely open or completely closed, and may not work properly when only partially open, as vibrations occur and the gate can become eroded.

Although they are built to withstand high pressures and temperatures, if there is circulation under such conditions through them, the valve seats can wear, which reduces the expected degree of sealing.

Thus, they are used when there is no circulation of high temperature fluid (normally closed), and when this circulation exists, at low temperature for emptying the equipment. Point 8 in Fig.1.

Fig. 5. Gate valve

1. Handle ' 2. Body ' 3. Stem ' 4. Gate ' 5. Retainer/packing ' 6. Seat

Needle valve

A needle valve is named after the needle-shaped conical stem that acts as a plug in an orifice which is usually of small diameter in relation to the nominal diameter of the valve, thus the shape of a needle or punch being necessary.

The movement of the fine threaded rod is slow and the flow section of the fluid is minimal until a good number of turns have been made.

They are used basically for isolation in replacement or maintenance operations for control components such as pressure gages, point 7 of Fig. 2 and more occasionally for visual levels, point 14 of Fig. 2. 2.

These valves are used in so-called instrumentation manifolds, which is a set of valves grouped as a unit, to operate different control components easily.

Fig 6. Needle valve

1. Body ' 2. Handle ' 3. Retainer/packing ' 4. Conical stem ' 5. Stem

Check valve

There are different designs of check valves, although all perform the same function with the same basic principle: being driven by the fluid pressure itself to allow it to flow in one direction and prevent it from returning to the pressurized part when the system pressure drops. They are, therefore, unidirectional to open in the direction of flow and to close in the opposite direction.

The decision of one design or another is based on the specifications of the individual equipment, types of connections to the pipes, construction materials, lower load losses, nature of the fluid, maintenance facilities and service temperatures and pressures, for example.

In thermal fluid equipment, it is normal to use flapper check valves (A) Fig. 7 or piston-type position ones (B) of Fig. 7 7 -.

In the clapper check valves, the disc is retained by a vertical or inclined stem which opens by oscillation movement caused by the flow, with the axis of rotation at one end.

In piston-type check valves, a disc reinforced with a spring and held by a pin lets fluid flow from the bottom up when there is pressure in the system.

Fig. 7. Check valves

A) Flapper · B) Piston

1. Body ' 2. Disc ' 3. External seal ' 4. Disc seal ' 5. Stem screw ' 6. Shaft stop ' 7. Hook ' 8. Spring ' 9. Stem ' 10. Bonnet

The main operations that require this auxiliary installation are:

  • Initial filling of the installation at start-up. It can be done from drums, from a large capacity tank or from the collection tank that has previously been filled from drums or vat.
  • Thermal fluid added due to shrinkage after a prolonged period of use. Generally, from drums.
  • Partial filling due to the expansion of the installation with new sets of consuming appliances. From vat or drums.
  • Partial emptying and subsequent filling of some branch of the installation for maintenance of the consuming device. Generally, to / from drums.
  • Emptying and subsequent filling of the load by changing the thermal fluid due to the end of its useful life.
  • Emptying and subsequent filling of the boiler due to repair thereof.
  • Emptying and subsequent partial filling due to repair or change of valve. Generally, to / from drums.

It is easy to conclude that these operations are one-offs ' it may take years from the start-up without any need for any type of action ' and only take place on rare occasions. Nevertheless, one must be able to be execute them safely and in a short period of time, in order to minimize the impact on production, since they all have to be done with the thermal fluid at a low temperature ' lower than 80 ° C -, and therefore with the production installation stopped.

That is why any installation of thermal fluid, has an auxiliary circuit for these operations; depending on its capacity and operational factors, these can be of different executions or complexity.

The filling / emptying circuit has a gear pump to be able to transport the fluid and a valve that allows us to decide from / to which equipment the operation is carried out ' see Fig.1 -.

Fig 1. Mesh gear pump for filling / emptying and auxiliary valves

The gear pumps are volumetric pumps, self-priming, with maximum operating temperatures up to 90 ° C in standard executions, whose usual applications, in addition to filling / draining in thermal fluid installations, include the transfer of fuels, lubricants, fats, and in general liquids of low or moderate viscosities.

They can be connected to the piping by flanges or threaded joints. Since the operating temperature will be around 80 ° C, it is customary to use threaded connection, as well as the group of auxiliary valves ' for example, valves 5, 6, 7 and 8 in Fig 3. -, except those that perform the role of separating the filling / emptying circuit from the installation, which are usually soldered connections ' valves 1, 2, 3 and 4 in Fig 3. -.

Fig 2.- All filling and draining operations

In Fig. 2., all the possible operations of loading and unloading the thermal fluid, and their possible origins and destination are shown. Operations from / to drums can also be considered from / to a tank, since it is no more than a large-capacity drum. The use of tanks ' as long as the quantity to be transported is important ' makes cheaper prices of the thermal fluid possible in exchange for more precision at the moment of carrying out the operation, in so far as the presence of the truck-tank at the plant entails a cost that it should be minimized as much as possible.

They can be reversible action or single direction (one-way). In the first case, from the control panel of the installation itself, it can be determined whether the operation will be filling or emptying. The valve must be operated solely to determine the origin and destination.

In the case of a non-reversible pump ' one-way -, from the control panel, only the pump is turned on. It is the action on the valves that will determine not only the origin and destination, but also whether the Operation is loading or unloading ' see Fig 3. -.

As well as the low temperature, we have to take some other precautions. Thus, if the unloading operation is intended to be carried out at the collection tank, it must be ensured that said tank is internally clean, without residual thermal fluid from previous operations or from water. Otherwise, the mixture of the thermal fluid load that is emptied with thermal fluid that has accumulated in the collection tank and that will obviously be very oxidized, can accelerate the degradation of said load and turn what should be a simple maintenance operation into a process that can shorten the useful life of the thermal fluid.

On the other hand, the presence of water or humidity in the tank, will mean that the new commissioning of the installation takes longer than expected, since this humidity will be introduced into the heating circuit and will force it to be eliminated, through slow and progressive warming.

Origin Destination Valve position 1 2 3 4 5 6 7 8 BI DR C C C C C A A C BI CA C C C A C A C C BI IN A C C C C A C C DR BI C C C C A C C A DR CA C C C A C C C A DR IN C A C C C C C A CA BI C C A C A C C C CA DR C C A C C C A C CA IN A C A C C C C C IN BI C A C C A C C C IN DR C A C C C C A C IN CA C A C A C C C C

Fig 3.- Filling and draining operations with a non-reversible pump.
Valve positions: O ' Open, C ' Closed

Ocher-shaded color in the table relates to illogical and non-standard operations.

The first step to determine, of course, is the fuel to be used.  Most of the time, cost is decisive; however, regularity of supply, the maintenance required and therefore the incidents that may have repercussions on production must be considered as well.

Always keeping in mind the location of the industry and the quantity of fuel to be used ' which can significantly affect the rates applied, the prices for most used fuels, in general terms, would be as follows:

  • Diesel: 0,082 '/kWh
  • Natural gas: 0.054 '/kWh
  • Propane: 0,115 '/kWh

Maintenance needs are always lower for gaseous fuels (e.g. natural gas and propane) than for liquids (e.g. diesel or fuel oil); therefore, the latter are not advisable for continuous industrial processes. Shutdown periods for maintenance are higher, especially for companies with limited maintenance facilities or those technically unprepared.

Fig 1. Monoblock burner: liquid fuel (diesel)

In processes in which continuous operation is critical, the option of a mixed gas/liquid fuel burner can be considered.  These burners have gaseous fuel as their main fuel, which does not require such habitual maintenance, but which can quickly be changed to a liquid fuel if there is a supply failure, a stock of which can be kept in storage for this type of situation.  Obviously, these types of burners are more expensive and complex, and so are recommended only in the aforementioned special case.

Burners for gaseous or liquid fuels have essentially the same operating scheme, but their properties can lead to some differences, due to their different nature and having to comply with the regulatory norms of their very different operation; see Fig 1 and Fig 2.  -.

Fig 2. Monoblock burner: gaseous fuel

Both types have a blower or fan driven by a motor, responsible for providing the combustion air required for burning.  As a general rule, low/medium power burners (up to about kW), the blower/fan and corresponding motor are coupled to the general burner housing, together with the combustion head. These burners are called 'monoblock' because of their compact structure.

Higher power burners, which can be of a considerable size, or those that are part of a combustion gas heat recovery system (see Fig. 3), can have the blower/fan and corresponding motor separated from the housing supporting the combustion head,  given the difficulty of properly supporting the fan, due to preheating the combustion air from these gases.

Fig 3. Combustion gases can be recovered.

These burners are called 'duoblock' as their configuration includes two groups of clearly differentiated components.

A fuel inlet, regulated by solenoid valves specific to each type of fuel and the corresponding safety components, is obviously necessary, as well as a combustion head with electrodes to produce the spark necessary for the ignition causing combustion.

Both types also have fuel pressure regulation to ensure proper combustion.  A deficiency in this parameter for gaseous fuels causes a reduction in specific damage, while it is one of the most common combustion failure faults for liquid fuels.

Preparing the fuel for combustion is very different in both types.  Spraying is essential for a proper mixture of combustion air and fuel in liquid fuel burners. This is performed by injectors or nozzles, according to the injected fuel pressure.

Liquid fuels with a high viscosity at room temperature (fuel oil) require heating elements in the burner itself, and even in its power supply network, to increase the supply temperature and decrease its viscosity for proper spraying to be achieved.

These added temperature and heating requirements are unnecessary in gaseous fuels (in which the fuel is not sprayed), but the injection speed does need to be controlled, to be compatible with the combustion air speed for an adequate mixture of both components for satisfactory combustion. There are therefore no nozzles, but the fuel supply holes to the combustion head are carefully designed.

An ignition safety device is also common in both types, normally either a photoelectric cell in liquid fuel burners or a probe or electrode in gaseous fuels.  These components detect whether there is a flame or not, as the final act of the ignition process, and block the burner if no flame has formed; thus forcing a manual reset of the burner to restart the process.

There are some significant differences in terms of safety and combustion controls depending on the type of fuel used.

Thus, installing an air pressure switch for gaseous fuel burners is obligatory, as it prevents ignition or blocks combustion if there is insufficient combustion air pressure.  In liquid fuel burners, this deficiency is covered by the safety device for lack of ignition or poor flame formation.

Also mandatory for gaseous fuel burners is a pre-sweep time,  which is a function of the burner power and the volumes of the combustion chamber and particular boiler smoke circuit. Air is taken through the blower before the ignition sequence ' and therefore without adding fuel ' to expel from the combustion chamber any possible residues of gases or unburned fuel existing from previous ignition attempts.

Determining the proper burner model for the boiler is quite simple and immediate, provided some small details are taken into account.

The burner must be able to overcome the overpressure of the boiler at the required working power.  To begin with, this power is not the same as that considered when determining the boiler for the production process.

If a kW boiler is needed, this considers only the consumer device requirements, the so-called net power which the system delivers; while the burner must supply the so-called gross power, which is the net power plus the energy losses that occur in the system, which are basically concentrated in the loss of energy due to the evacuation of combustion gases and to a lesser extent due to structural losses to the environment through the boiler.

The gross power is of the order of 10-20% more than the net power and depends on the boiler design, service temperature and fuel.  Therefore, for a boiler of kW net power, a burner with power of - kW is required.

The boiler overpressure is the loss of load or pressure in the internal smoke circuit.  In other words, the burner blower/fan must provide sufficient pressure to the gases formed in the combustion, so that their flow at the maximum gross power required by the system can be achieved by the entire smoke circuit.

The boiler overpressure is a data point that must be provided by the manufacturer, without which it is impossible to correctly choose the burner selection criteria. This is explained below.

Fig 4. Burner operating curve

Fig 4. shows the burner operating curve. If it has been determined that the system requires 350 kW of gross power, it may be thought an appropriate burner would reach 410 kW.  However, this power of 350 kW is supplied by the burner only if the boiler overpressure for this power is equal to or less than 3 mbar: the blue line on the graph. If the boiler overpressure is 6 mbar (the red line on the graph), the burner blower may not supply that pressure for the required flow and supply around 310 kW, which would not be appropriate for the selected burner.

The combustion chamber dimensions should also be considered as a requirement of the boiler.  The combustion chamber must be able to adequately accommodate the flame dimensions as produced by the burner.  This is especially important in liquid fuel burners, since differences in flame length can be significant depending on the injector or nozzle features that the burner has installed; while the influence of the pressure of the fuel injected is well established for flame diameter.

Fig 5. Flame length/nozzle spray

The flame diameter must be lower than that of the combustion chamber, as either contact or proximity of the flame to the coils on the side of the combustion chamber could lead to their destruction by excessive heating.  Also, the flame length must be considerably less than the total combustion chamber length in order to prevent rapid deterioration of the combustion chamber bottom, regardless of whether refractory concrete or a cooled metal plate is used for this.

Finally, the boiler combustion chamber dimensions have a decisive influence on the quality and type of combustion that the selected burner can provide.

Nitrogen oxides are inorganic compounds of nitrogen and oxygen produced in combustion.  They are termed NOx, as there are different types according to their ratio of nitrogen and oxygen, and their emission levels are regulated by environmental and health standards due to their adverse effects on health.

NOx levels emitted during combustion can vary substantially with the same burner, according to the combustion chamber dimensions.  This is especially critical when the burner selected is not specifically for low NOx emissions. This does not imply that the national regulations in force cannot be satisfied for environmental emissions; however, it must be ensured that the burner is properly adjusted to the boiler, and specifically its combustion chamber.

Depending on the production system operating features, the burner can be regulated differently to deliver the required power.  The objective must always be to minimize burner shutdowns and subsequent removal, so that the power supply is as stable and uniform as possible.

In fact, each burner shutdown involves cooling the combustion chamber, only to be re-heated when starting up again.  Thus, fuel is used only to re-heat the chamber and is not transmitted to the heat transfer fluid (in our case thermal fluid), resulting in lower boiler equipment performance.

This cooling has a 2-fold cause: the spontaneous circulation of air due to the convection produced by the temperature difference between the combustion chamber and the ambient air introduced in the boiler (although this is relatively small), even without the connection of the fan; and the air intake through the blower, prior to the ignition sequence, to expel from the combustion chamber possible excess gas or unburned fuel residues from previous ignition attempts in gaseous fuel burners as part of the mandatory pre-sweep safety system.

The best regulation system for more stable burner operation is a modulator, which supplies fuel regularly between a minimum and a maximum value.  As long as the consumption is not lower than the minimum allowed by the modulating regulation system, the burner will not go out and will not have to be re-started; thus providing stable working operation and significant energy saving.

Obviously, this regulation system involves a greater up-front cost when acquiring the burner and must be weighed against the gain in performance that use of this regulation provides.  In most cases, the installation of the modulating regulation system is appropriate from a financial point of view.

The other significant functional advantage is the service temperature stability that modulating regulation provides compared to other one- and two-stage regulation systems.

The one-stage regulation system ' also called 'on/off' ' is the simplest.  It consists of delivering the absolute maximum burner power for whatever energy is demanded by the system, no matter how small.  This means that excessive energy is being supplied at certain moments which requires an immediate response from the sufficiency system and therefore of absolute closure of the energy input, leading to a 'sawtooth' type of supply; see Fig. 6: Some points have excessive fuel supply and others do not meet those demands when the system requires energy and the burner is still in the process of starting up.

This two-stage regulation system ' also called 'all/little/nothing' ' smooths the deficiencies of the one-stage regulation system.  The new intermediate stage, between the maximum power and turning off the burner reduces both the sawtooth changes and the burner possibilities/system requirements incompatibility points.

This dysfunctionality in the one and two stage regulation systems means that the actual system service temperature, compared to the required service temperature, also has a pronounced sawtooth property with differences that can range between +3 and -10°C approximately, according to the process.

Fig 6. Regulation types

In modulating regulation, as long as the energy required by the production system is not less than the minimum supplied by the burner without shutting down (between 1/6 and 1/12 of the maximum depending on the model and power), the difference between the set or required temperature and the actual temperature of the system will be about ±1°C; thus providing a stable service temperature and the possibility of higher quality production.

A Comprehensive Introduction To Thermal Oil Boilers: Components ...

In industrial heating systems, water is typically used as the working fluid and the medium for heat transfer. However, at high temperatures, the use of this fluid requires extremely high operating pressures, which can be costly and challenging in terms of safety. Therefore, thermal oil boilers are used in applications that require high temperatures. Reaching high temperatures with thermal oil is possible at pressures close to atmospheric pressure, whereas achieving similar temperatures with water and steam requires much higher pressures.

Thermal oil boiler

One type of industrial boilers in the water-tube category is the thermal oil boiler, where thermal oil flows through the pipes, heating the water surrounding them within the boiler shell. The thermal oil boiler is an advanced type of boiler that is widely used in various industries to provide the necessary heat for systems. Unlike steam or hot water boilers that use water as the heat transfer fluid, thermal oil boilers use thermal oil to transfer heat. These oils are capable of withstanding high temperatures (up to about 300 degrees Celsius or more) without boiling or requiring an increase in system pressure.

Advantages of using thermal oil boilers

Thermal oil boilers have numerous advantages due to their unique features, making them a suitable choice for industrial applications. Below are some of these advantages:

Operation at high temperatures

One of the main advantages of thermal oil boilers is their ability to raise the thermal oil to temperatures of up to 300 degrees Celsius or higher, without the need for high pressure in the system. In steam systems, reaching such temperatures requires a significant increase in pressure, whereas in thermal oil systems, this issue does not occur.

Enhanced safety

Thermal oil boilers, due to the absence of high pressure requirements, carry fewer risks compared to water and steam boilers. The risk of explosion in these systems is significantly lower.

Prevention of scale formation and corrosion

In steam boilers, scale usually form in the tubes and equipment, which can lead to reduced efficiency, increased maintenance needs, and higher costs. However, in thermal oil boilers, due to the use of thermal oil, the system does not require frequent cleaning.

Longer system lifespan

Due to reduced corrosion and no scale formation, thermal oil boilers generally have a longer service life compared to steam or hot water boiler.

Lower maintenance costs

Thermal oil boilers have lower maintenance and operating costs compared to other types of boilers, as thermal oil does not need frequent replacement, and there is no requirement for regular cleaning and repairs.

Disadvantages of thermal oil boilers

While thermal oil boilers offer several advantages, they also have some disadvantages:

High flammability

Thermal oil is flammable at high temperatures. If the pipes, fittings, or tanks of the system are damaged and the oil leaks out, it can come into contact with hot surfaces or flames, potentially causing a fire.

Higher cost of thermal oil

The cost of acquiring thermal oil is higher compared to water and requires careful management.

Environmental impacts

In case of leakage, thermal oil may damage the environment and demands proper safety precautions.

Use of high-temperature pumps

For circulating thermal oil in a thermal oil boiler, specific pumps are necessary. These pumps must be capable of tolerating high temperatures, as thermal oil in these systems can reach up to 300 degrees Celsius or beyond.

Thermal oil boiler components

The main components of a thermal oil boiler include the furnace, heat coil, and burner, each of which is described in detail. Additionally, other essential parts such as the expansion tank, oil circulation pump, control valves, and more are also discussed, as they play a critical role in the boiler's operation.

Furnace

This is the heart of the boiler, where the combustion process takes place. In the combustion chamber, fuels such as natural gas, diesel, or heavy oil are burned, releasing thermal energy. This thermal energy is then transferred to the heating coils, which carry the thermal oil.

Heating coil

These are a network of tubes located inside the combustion chamber. The tubes are coiled around the flame to provide a larger surface area for contact with the hot gases produced by combustion. The thermal oil flows through these coils, absorbing the heat produced by the combustion. The number and arrangement of the coils vary depending on the boiler's capacity and design.

Burner

In a thermal oil boiler, the burner is responsible for producing the necessary heat by burning fuels like natural gas or oil, and then transfer this heat to the thermal oil within the heating coils.

Control system

This system consists of electronic components and sensors which monitor the boiler's performance. It measures the pressure, temperature, and oil flow rate, ensuring the boiler operates safely and optimally. Advanced control systems have the ability to adjust automatically and provide alerts.

Oil pump

The oil pump is responsible for circulating the thermal oil throughout the system. It must be capable of directing the oil into the coils at the correct flow rate and pressure. Given the high temperature of the oil, these pumps are built to endure and function properly at high temperatures.

Control valves

These valves are used to regulate the pressure and flow rate of the oil in the system, controlling the oil's inlet and outlet flow.

Expansion tank

The expansion tank serves to compensate for the volume changes of the oil caused by thermal expansion. As the oil heats up, its volume increases, and if there isn't enough space for this expansion, the pressure within the system rises significantly. The expansion tank allows the oil to expand without causing excessive pressure buildup. Typically, the expansion tank is located at a higher elevation than the boiler and other equipment, which creates a static pressure in the oil circuit, keeping the oil in its liquid phase and preventing it from vaporizing.

A key function of the expansion tank is to provide make-up oil. It serves as a storage for thermal oil, ensuring that when oil levels decrease due to leakage or evaporation, extra oil is injected into the system.

Since oil is highly flammable at high temperatures, one way to prevent explosions is inert the space above the tank. This is done through a process called blanketing, where an inert gas like nitrogen fills the upper space of the tank, preventing oxygen and air from entering.

Thermal oil used in thermal oil boilers

These oils must have a high heat capacity to transfer heat effectively. Thermal oils need to be stable at high temperatures and retain their properties. Resistance to oxidation is crucial to prevent the formation of deposits in the system. The oils should have a high boiling point to avoid vaporization at elevated temperatures. Additionally, they should not cause corrosion in the system components and must be environmentally safe.

Classification of thermal oils

Thermal oils are divided into two main categories: mineral oils and synthetic oils. More details about them are explained below:

Mineral oils

The largest group of thermal oils consists of mineral oils. These oils are obtained through the distillation of crude oil in refineries. The operational temperature range for mineral oils is from -10°C to 300°C, which is why they are used for temperatures below 300°C. Mineral oils are more economical than synthetic oils and have less environmental impact. Paraffinic and naphthenic oils are examples of mineral oils.

Synthetic oils

These oils are produced through chemical synthesis processes. Synthetic oils, also referred to as aromatic oils, are based on a benzene structure. The operational temperature range for these oils is from -20°C to 400°C. Their aromatic structure makes them thermally more stable than mineral oils, which is why synthetic oils are used for temperatures higher than 300°C. Synthetic oils offer higher efficiency and greater heat transfer at elevated temperatures. Poly glycol fluids, ester and diester compounds, and silicone-based oils are types of synthetic oils.

Commonly used thermal oils include:

  • Behran thermal oil (Behran Hararat 32)
  • Shell thermal oil S2
  • Total Seriola eta thermal oil 32
  • Theminol thermal oil 66

Operation of a thermal oil boiler

Thermal oil boiler functions by circulating thermal oil through a closed system. The heating process is carried out by a burner that uses either gas or liquid fuel. The process of heating the oil is carried out by a burner that uses either gaseous or liquid fuel. The burner ignites the fuel, generating thermal energy, which is transferred to the oil. The thermal oil then flows through a series of heating coils situated inside the boiler furnace. These coils are usually spiral-shaped to maximize contact with the hot gases produced during combustion.

In this way, the oil inside the coils is heated by absorbing heat from the hot gases. The thermal oil is then transferred through piping to heat exchangers or other industrial systems. After transferring its heat, the thermal oil cools down and the cooled oil returns to the boiler to be reheated. This cycle continues continuously, supplying the necessary heat for the processes without interruption.

Types of thermal oil boilers

Thermal oil boilers are classified into two categories based on their installation method and overall structure: horizontal thermal oil boilers and vertical thermal oil boilers. They are also categorized according to the type of fuel used: gas-fired thermal oil boilers and electric thermal oil boilers.

Vertical thermal oil boiler

This type of thermal oil boiler is typically produced in smaller capacities and is commonly used in locations with space limitations. Due to gravity, the discharge of hot oil in these boilers occurs more quickly.

Horizontal thermal oil boiler

Thermal oil boilers of the horizontal type are manufactured in larger capacities than their vertical counterparts and offer higher efficiency. In horizontal thermal oil boilers, accessing different parts of the boiler, as well as performing maintenance and inspections, is more convenient.

Electric thermal oil boiler

This type  uses electrical energy to heat the thermal oil instead of fossil fuels (such as gas or oil). In these boilers, heating elements generate the required heat to warm the oil. The heated oil is then transferred in a closed-loop system to different sections of the system to supply the necessary heat for processes. The non-use of fossil fuels in electric thermal oil boilers reduces environmental pollutants. Due to the high flammability of thermal oil at high temperatures, electric thermal oil boilers are recommended for lower capacities instead of gas-fired thermal oil boilers.

Applications of thermal oil boilers

Thermal oil boilers are used in a wide range of industries. One of the most important applications of thermal oil boilers is in industries where heat transfer is done indirectly. This makes them highly effective for heating flammable materials like crude oil and natural gas. Some of the uses of thermal oil boilers are as follows:

Wood industry

Thermal oil boilers play a crucial role in the processes related to the production of wood products in the wood industry. By utilizing these boilers, the moisture within the wood is gradually evaporated in a controlled manner, which improves the wood's longevity and stability.

Textile industry

Thermal oil boilers are used as the primary heat source in dryers and dyeing machines for fabric and fiber processing. These boilers, by providing a uniform and precise temperature, help improve color absorption and facilitate the rapid drying of fibers.

Chemical industry

Thermal oil boilers are used in the chemical industry due to the high temperature and heat requirements for producing solvents, adhesives, and resins. They are also employed in the production of bitumen, waterproofing membranes, asphalt, and the heating of heavy petroleum materials.

Want more information on Steam Generator? Feel free to contact us.

Thermal oil boilers: Efficiency, Safety, and Lower Costs