10 Questions You Should to Know about centrifugal humidifier

14, Apr. 2025

 

How to Choose the Best Humidifier for Your Commercial Application

The humidifier you select for your commercial project matters. The type of humidifier you choose and the installation logistics involved will significantly affect everything from air quality to OSHA compliance, so you must correctly determine the right humidifier for optimal commercial air management.

Click here to get more.

A commercial humidification system allows you to increase or decrease humidity levels for industrial, healthcare, education, and other public environments. While most buildings have heating, cooling, and ventilation systems, only a fraction have a humidification system. This is a significant oversight in commercial air quality management because optimal air moisture offers a variety of benefits, including the following:

  • Health: Low relative humidity indoors contributes to higher rates of infection by airborne-transmitted diseases, as well as increased respiratory problems.
  • OSHA Compliance: OSHA dictates the acceptable range of indoor humidity is 20–60%.
  • Energy Efficiency: The expense of a humidifier can be offset by minimizing heating costs, damage to equipment, adverse health issues, and related costs (absenteeism, insurance claims, and more).
  • Commodity Protection: Commercial environments, such as warehouses and laboratories, need to control humidity within a 5–10% range of setpoint to protect goods and other commodities.
  • Static Electricity Reduction: Static electricity can damage electronics and is unsafe in the presence of hazardous or explosive materials.

Two Types of Humidifiers for Commercial Air Management

Engineers usually choose from two types of humidifiers; isothermal or adiabatic. Each offers advantages and challenges.

Isothermal Humidification

In this system, external thermal energy produces vapor or steam. Air temperature remains nearly constant. This system offers exact control of humidity and doesn’t increase heat load space. It’s also an exceptionally hygienic system (medium is above 212° F, or 100° C). However, an isothermal humification system does require an outside heat source such as steam, hot water, electricity, or gas.

Adiabatic Humidification

In this system, water (as opposed to steam) is introduced into the air. Space air or airflow provides the energy for vaporization. No heat is added from an external source.

An adiabatic humidification system may offset the cooling load, particularly in shoulder seasons, resulting in energy savings. This system also offers precise humidity control and is a good option when steam or gas is unavailable. However, more extended air handling units (AHUs) are potentially needed due to longer absorption distances. In some applications, additional heating capacity might be required.

Where Will You Install Your Humidifier?

There are two locations to install a commercial humidifier. A ducted humidifier is the most common installation. In this configuration, vapor is distributed via the ductwork. That vapor can be produced either inside or outside the ducts. This system is popular because it doesn’t interfere with the existing layout, and it can utilize existing fans and heating systems to accomplish the distribution and reheating.

However, it does require labor-intensive inspection and maintenance. There is also a potential risk of the ductwork suffering from unsupervised condensation, mold, and bacteria.

A self-contained humidifier doesn’t rely on ductwork. Instead, it distributes vapor within the space, typically by a packaged unit. These are less common than ducted humidifiers, but they are effective when you only require humidification in a single zone, it’s difficult to retrofit the existing space, or you want to control the humidifier separately from the HVAC system. However, self-contained units can offer floor access for easier operation, inspection, and maintenance. Finally, self-contained models could require several units for adequate distribution, which would affect cost.

Which Humidification Technology Is Best for Your Commercial Air Management?

While there are two main types of humidifiers (isothermal and adiabatic) and two primary types of installation (in-duct and self-contained), many technologies have been developed for use in various applications. By understanding each system’s advantages and disadvantages, you will find the most cost-effective and practical solution for your space. Here’s a quick overview of the most popular humidifier technologies;

Centrifugal Atomizing Humidifier

  • Adiabatic
  • Atomizing
  • Installs in space or distributes via ductwork
  • Flush or drain needed in duct
  • Relatively inexpensive to install and maintain
  • Tends to be noisy
  • Maximum capacity is about 20 pounds per hour

Compressed Air Nozzle Humidifier

  • Adiabatic
  • Atomizing
  • Installs in space or distributes via ductwork
  • Flush or drain not needed
  • Relatively inexpensive to install (unless the compressed air is not already available)
  • Inexpensive to maintain
  • Electric energy costs for compressed air service can be high
  • Tends to be noisy

Direct Injection Humidifier

  • Isothermal
  • Installs in ductwork or AHU
  • Flush or drain not needed
  • Steam-powered
  • Relatively expensive to install if supply steam is not already available
  • Inexpensive to maintain
  • Steam-related energy costs can be high
  • Always ensure boiler treatment chemicals are safe for steam injection and introduction into supply air

Gas Fired Humidifier

  • Isothermal
  • Uses gas burner instead of electricity
  • Installs in mechanical room and distributed via ductwork
  • Flush or drain needed
  • Relatively inexpensive to install and run if gas is already in place

Steam to Steam Humidifier

  • Isothermal
  • Heated by steam from boilers
  • Installs in mechanical room and distributed via ductwork
  • Flush or drain needed
  • Energy efficient
  • Relatively inexpensive to install

Electric Resistance Humidifier

  • Isothermal
  • Installs in space or distributes via ductwork
  • Flush or drain needed
  • Electric heat source
  • Relatively inexpensive to install and maintain, but electric energy costs can be high

Electrode Humidifier

  • Isothermal
  • Installs in space or distributes via ductwork
  • Flush or drain needed
  • Electric heat source
  • Relatively inexpensive to install and maintain, but electric energy costs can be high

Heated Pan Humidifier

  • Isothermal
  • Installs in space or distributes via ductwork
  • Flush or drain needed
  • Steam-powered
  • Installation costs can be high, especially if a steady steam supply is not already in place
  • Relatively low maintenance, but since it uses steam, energy costs can be substantial

Pressurized Water Humidifier

  • Adiabatic
  • Atomizing
  • Installs in space or in the ductwork
  • Flush or drain needed in duct
  • High installation costs, but maintenance is generally low
  • Runs on electric but is energy efficient and relatively inexpensive to operate

Rigid/Wetted Media Humidifier

  • Adiabatic
  • Evaporative
  • Installs in space or in the ductwork
  • Flush or drain needed
  • Comparatively inexpensive to install and operate
  • Relatively high amount of maintenance requires to manage bacteria and mold which accumulates in the basin 
  • Low risk of oversaturating the air
  • Fairly imprecise control of relative humidity within the space

Ultrasonic Humidifier

  • Adiabatic
  • Atomizing
  • Installs in space or in the ductwork
  • Flush or drain needed
  • Relatively expensive to install
  • Maintenance is generally low, other than replacing disks every 10,000 hours
  • Runs on electric but is energy efficient and relatively inexpensive to operate
  • Maximum capacity is about 80 pounds per hour

General Considerations When Selecting a Commercial Humidifier

When researching humidifiers for your commercial space, remember that every humidifier type, barring direct steam, requires a water service. This can either be domestic water or demineralized (DM), deionized (DI), or reverse osmosis (RO) water. In addition, some (but not all) humidifiers require treated water.

Water treatment tends to add significantly to installation and operation costs, but it can also improve the humidifier’s overall operational performance. Using the right kind of water can also minimize maintenance intervals and reduce mineral fallout in the space. Note that using softened water can reduce maintenance intervals (by reducing scaling on the humidifier components), but it can increase mineral fallout.

Finding the Right Humidifier Distributor for Your Application

Humidifier Facts - HVAC School

Humidifiers are a big part of HVAC systems in dry locations, especially in the winter. I have no experience with them personally because they aren't prevalent at all in Florida.

I asked some of the HVAC School contributors to weigh in with some of their top humidifier tips. Thanks to Nathan Perney, Steve Domansky, and Allen Pavolko for weighing in.

First, Nathan Perney gives us a detailed look at humidifier selection and sizing:

We do a LOT of humidifiers here in dry old Denver.

My take on selection, like most things I do, is a little different than most.

If we look at section 27 in the eighth edition of Manual J, there is a great methodology for determining winter humidification load.

It's pretty straightforward.

First and foremost, get a good estimation of wintertime infiltration and exfiltration. That’s right! Set up the blower door. This step rarely happens.

Next, determine your target indoor humidity. That part is a little tricky. Manual J shows some calculations for determining winter humidity that will keep the building safe. Safe means dry. Dry means no hidden condensation. Page 139 in the Builder Guide to Cold Climate Construction shows the same calculation. I like Lstiburek’s approach over Rutkowski with regard to the humidity target. It’s the same math; I’ve just been a disciple of Lstiburek for longer. Haha.

Once you get the target humidity, convert your CFM of air leakage to a mass airflow of air leakage. Let's say we have a house leaking 100 CFM at my air density of . lb per cu/ft; that would be 6.13 lbs of air per minute.

At this point, get out your psychrometric chart. (Here is the one I use often.)

For more information, please visit Ant.

Now, convert your mass air leakage to grains of air leakage. 6.13 lb/min of air leakage at 50% RH at 70°F = 66.6 grains per minute x 60 minutes x 24 hours = 95,904 grains per day. WOW! We know there are 7,000 grains per pound. That gives us 13.7 pounds of water a day, or about 1.7 gallons per day, or .07 gallons per hour.

All right! Now we can take the gallons per hour and look at the humidifier specifications:

Based on the Aprilaire data, we might want the 400, 600, or 700 series.

The manufacturer alludes to this calculation in the performance information:

The really interesting thing is the air leakage component. Older leaky houses need WAY more humidity than new tight houses. Just as the warmth from our heating systems leak out before we can feel it. In old, leaky buildings, the humidity leaks out before you can sense it. However, in newer, tighter houses, we can have problems. In fact, I have seen several new, tight houses over-humidifying and having serious condensation issues. Water is amazing; it moves mountains. It also destroys buildings better than pretty much anything—aside from explosives. The good thing is cold air is dry air, so drying buildings in the winter is much more realistic than during the summer.

Wait. What did I just say drying a building during the winter? You better believe it. Depending on what you do in your home, how tight your home is, and what the building assemblies are comprised of, you may well need to dry the building during the winter. Just ask the Canadians. As building codes are pushing building tightness tighter and tighter (this is a good thing), we will see more over-humidification issues. Over-humidification of new buildings in cold climates is a very serious issue we will begin seeing more and more.

The biggest install failure is not getting the drainage correct. Test the drains, or you're asking for problems. Test the operation, or you're asking for problems. Make sure they turn on and off when you ask them to. I had a job recently where a steam humidifier was wired to create steam any time the unit had power. The installer wired the relay incorrectly, and we had 75°F 70% humidity in the house. The windows were raining. It was awesome. Like anything, read the dang manual. Steam humidifiers are very temperamental, so if you don't follow the manual, you will have problems. Steam humidifiers have very specific tolerances for where and how they can and cannot be installed. One thing to be wary of is that you are setting up a steam humidifier to operate with a constant fan. Check the velocity of the air during the fan-only mode. If the air is not moving fast enough, you will get condensation in the ductwork (this is bad). Another common install error is the HUM terminal on the control board may r 24 VAC. All residential humidifiers that I  know of require 24VAC to control the unit. If you don’t install an isolation relay, you will fry the solenoid valve.

—Nathan Perney

Allen Pavolko shared his perspective from the Eastern US:

Proper Selection

Choosing the right humidifier for your home depends on multiple things. These include but are not limited to the size of the home, heating system, ductwork availability, and geographic location. Where I live (Southwestern NY, near Buffalo), most homes that have a forced-air furnace have a bypass humidifier installed to help keep the relative humidity in the living space during those dry winter days. Due to cold air not being able to hold as much moisture, we tend to lose humidity in the wintertime. That can lead to higher counts of airborne viruses staying alive in the air, static electricity buildup, drier skin, improperly sealed/treated wood cracking, etc. Keeping the humidity between 30% and 50% in the living space year-round can help battle all of those things.

The biggest element of choosing a humidifier, in my opinion, is what ductwork you have available to attach a system to. If you have enough room to install a bypass humidifier, you can treat up to a 4,000 sq ft house with one, but you need ample room to mount the humidifier and pipe it to the other airstream. If you don’t have the room to do that or have a bigger house, you can do a power humidifier. These have a fan built into them to push the air through the media and can treat up to 4,200 sq ft. The last option for ducted systems is a steam humidifier, which can be remotely installed and piped into the airstream. These systems can treat up to 6,200 sq ft of living space, take significantly less space to install, and can be remote, as I stated prior.

Note: Obviously, coverage size is specific to the humidity needs and design of the home, as Nathan pointed out.

If there is no ducted system in the space, then you can get a non-ducted system that just adds water vapor to air and lets natural convection currents take over to distribute. Or you can use a steam humidifier paired with a fan pack to distribute the water vapor to a central location.

How to Install 

The best scenario is to install the humidifier unit on the supply air plenum with it piped over to the return air drop. Our local rep for a well-known humidifier manufacturer advised using hot water for the feed tube as often as possible, as it helps the water evaporate faster. Always utilize a flow restrictor on the water supply, as not to add way too much water to the evaporation pad. Together, these things make for the best, in my opinion, way to get humidified air into the living space. The hottest air passes over already warm water on the pad and evaporates as quickly as allowed. This goes into the airstream and passes back through to the house. If possible, install an outdoor air temperature sensor to control humidity levels in the home automatically.

Common Mistakes

The most common mistake I have seen in the field is failing to make sure the humidifier is level and plumb. This can cause the unit to leak!

Another common mistake is removing the fabric out of the distribution tray because it looks and feels gritty. This is there for a reason, and that is to allow the water to flow through each distribution channel evenly.

Common Service Failures 

I have often seen a solenoid valve misdiagnosed as being bad due to water not flowing through it. I live in an area with high mineral content in the water; this, coupled with the small diameter water piping and small orifice, often leads to a plugged-up orifice/flow restrictor.

—Allen Pavolko

For more information, please visit centrifugal humidifier.